Each Standard Graphic is validated with the following rules:
Info Rules:
All Validated
Objects
Any objects
that were found in the MSEA Binder Database that aren't graphic
objects.
All Validated
Graphic Objects
Any graphic
objects that were found in the MSEA Binder Database. If the object
is a buttonnode and the ClassID of the node = 344, it is considered a graphic
object. Note: This may be a problem since it appears that the
ClassID can be incorrect if an object is copied and pasted.
External
Links
All external
hyperlinks. Anything that has "://" in an object reference.
All Aliased
Links
Any nodes that
have the "Aliased" property checked.
Elapsed
Time
Total time in
seconds to validate the graphic object
This Graphic Object
Name
The name of the
current graphic object being validated.
Warning Rules:
Blank Object
Reference
A blank object
reference was found.
Template Links In
Template File
Occurs if
aliased links to another template graphic are found.
System Name
Mismatch
Occurs when the
GMFDocument in the SCT database reports a graphic system object reference that
is different from the actual graphic object reference. This can occur when
a graphic is copied and pasted as another graphic name, but the new graphic was
never edited and saved. The system references from the copied system still
remain in the new graphic.
Aliased Links Were
Found - Re-Run using Follow Links Enabled.
Occurs when at
least one aliased link was found and the Follow Links function was not
enabled.
Error Rules:
Invalid
Binding
Object
reference didn't match any object reference in the MSEA Binder
Database.
Invalid Graphic
Binding
Object
reference didn't match any object reference in the MSEA Binder
Database.
Failed To Set
Binding Status
A validated
point wasn't flagged as bound in the database. Problem setting the
flag.
Error Loading XML
File
Problem loading
the XML graphic data.
No Graphic Has Been
Uploaded
A graphic
background was not found in the SCT database.
Error Reading SCT Database
No Graphic Objects
Found
No nodes were
found in the SCT database.
GMFDocument Version
Not Tested
Only version
4.1 has been tested using the Standard validator.
Failed to Register
Graphic
Failed to
create an entry in the Graphic Mapping table in the MSEA Binder database.
If this error occurs, the points in graphics information won't be created
in the database, but the validation for the objects will.